XQC1600

Mobile Generator Sets

Details

Rating
1515 ekW (1893 kVA) Continuous

Frequency
50/60 Hz

Voltage
230 - 480 V

Contact

Foley Equipment Sales

+1 (316) 943-4211

Request a Quote

Overview

1515 ekW Mobile Diesel Generator Set

This rental generator set extends the Caterpillar line of rental power options improving efficiency and reduced owning and operating costs. The XQC1600 is equipped with an enhanced control system, designed to reduce installation and startup time. It is configured to switch between 50 and 60 Hz ratings at the press of a button. The control system features plant control programming and simulation, allowing complete system testing prior to generator set startup. Advanced product autonomy and monitoring capabilities reduce on-site manpower support requirements, minimize operator exposure to hazards, and permit site performance and maintenance data to be viewed, archived, and analyzed conveniently. Ideal in a stand-alone environment, combined with dozens of units in a power plant solution, or supporting utility systems worldwide.

Benefits

ambient capability

Provides full power even on hottest days of the year

high-cube container

9-High Stack, CSC Certified - Designed and built for robustness, safety and transportability

oil tank

Engine mounted oil level regulator maintains oil pan levels in extended run applications

Features at a Glance

Rental Ready
Extensive range of rental ready features to meet job requirements and applications.
Fuel/Emissions Strategy
Low BSFC and Low Emissions* ratings, switchable via Cat Electronic Technician (ET) * Does not conform to EPA/EU emissions standards
Reliable, Fuel Efficient Cat Diesel Engine
The compact, four-cycle Cat 3516C turbocharged-aftercooled (SCAC) diesel engine provides proven durability and dependability Best-in-class fuel economy Fuel system operates on a variety of fuels 50/60 Hz switchable with neither software re-flashing, nor iron changes required Other engine features include: electric fuel priming, individual cylinder temperature monitoring, and extended filter change intervals
Cat EMCP Control Panel
EMCP 4.3 control panel offers engine and generator monitoring and protection On-Package Auto Paralleling Controls AGC-4 provides paralleling, load sharing, VFD control, and additional generator protection
Cat Generator
Cat SR5 generator designed to match the performance and output characteristics of the Cat Gas engine. Class H insulation operating at Class F temperature for extended life Coastal insulation protection and anti-condensation space heaters Integrated Voltage Regulator (IVR) for fast response in demanding applications
Cooling System
Provides 49°C (120F) ambient capability at 50 Hz & 60 Hz at the IPP Rating at 750m (2,460 ft) above sea level Variable frequency fan drive with smart fan control Energy efficient electric drive fans
Sound Attenuated Container
Meets 75 dB(A) (50 Hz) / 81 dBA (60 Hz) at 7m (23 ft) 40' ISO high cube container, 9-high stack CSC certified Service and Personnel doors Externally-accessible controls
Cat Connect
Remote monitoring for fleet management and asset tracking.
Reduced Environmental Impact
110% spill containment of onboard engine fluids Positive crankcase fumes ventilation
Single-Source Supplier
Generator set manufactured in ISO 9001:2000 compliant facility Package factory designed and production tested
Worldwide Product Support
Cat® dealers provide extensive post sale support including maintenance and repair agreements. Supported 100% by the Cat dealer with warranty on parts and labor. Extended Service Coverage (ESC) options available for coverage beyond the Standard Warranty period

Specifications

Full Specifications

Generator Set

Rating
1515 ekW (1893 kVA) Continuous

Frequency
50/60 Hz

Voltage
230 - 480 V

IPP Overload 50Hz
1590 kW (1987 kVA)

IPP Rated 60Hz
1705 kW (2131 kVA)

IPP Overload 60Hz
1790 kW (2237 kVA)

Engine

Engine
Cat 3516C

Fuel
Diesel

Dimensions

Height - Without Chassis
114 in

Length - Without Chassis
480 in

Weight - Without Chassis, With Fuel, Lube Oil and Coolant
70000 lb

Width - Without Chassis
97.5 in

Equipment

Standard Equipment

Cat 3516C Heavy Duty Diesel Engine

  • Heavy duty, dual element, PowerCore air cleaners with service indicators
  • Triple, primary fuel filters with water separators and bypass valves for on-the-fly filters changes
  • Secondary fuel filters on engine
  • Full flow oil filters with water-cooled oil cooler. Requires API CI-4 or higher lube oil
  • Lubricating oil system includes make-up system (113-L tank), oil drain lines routed to the engine rail, and quick evacuation system for faster, cleaner oil changes
  • Jacket water heater (9 kW, 3-phase 480VAC) with electric pump
  • Fuel cooler and electric fuel priming pump
  • Electronic differential pressure monitoring of all filters
  • Electronic ADEM™ A4 engine controls
  • Dual 24V electric starting motors

SR-5 Generator

  • Double-bearing, 1844-Frame, SR-5 generator with anti-condensation space heaters (1.2 kW, 480V)
  • Brushless, form-wound, permanent magnet excited, thouree-phase, 4-lead design
  • Class H insulation operating at Class F temperature for extended life
  • Cat Integrated Voltage Regulator (Cat IVR)
  • Stator winding and bearing temperature detectors monitored by RTD module
  • Metallic mesh generator air inlet filters (2)
  • System 4 insulation protection

40' ISO high cube container

  • 9-High stackable, CSC certified
  • Sound attenuated, hinged, radiator intake louvers
  • Sound attenuated package air intake louvers with foldable awnings
  • Five (5) lockable personnel doors with panic releases
  • Interior walls and ceilings insulated with 100 mm of acoustic paneling
  • Side bus bar access door with external access load cable connections
  • Shore power via distribution block connections for jacket water heater, battery charger, space heaters, and generator Anti-condensation Heaters
  • Six (6) DC lights with 60-min timer
  • Single-wall, 946-L (250gal) fuel tank; certified to BS799-5
  • Solenoid fuel fill control valve for automated filling
  • Sound attenuated to 75 dB(A) (50Hz) 81 dB(A) (60Hz) at 7m (23 ft)
  • Four (4) 1400-CCA, Group 4D, maintenance-free batteries, and 50A battery charger
  • Insulated exhaust silencer with 1.8m (6ft) stainless steel exhaust stack for increased site power density
  • Engine vibration isolators
  • Easy drain access to standard fluids
  • Standard Cat decals (Optional) and painted Cat Power Module White

Cooling

  • Cooling package provides 49°C (120°F) ambient capability (50 & 60 Hz) at IPP Ratings @ 750m (2,460 ft)
  • Vertical, non-stacked radiator cores with dimpled fins and vertical air discharge
  • Variable frequency fan drive with smart fan control
  • Cat Extended Life Coolant (ELC)

Generator Controls and Protection

  • EMCP 4.3 generator set controller
  • Automatic start/stop with cool down timer
  • Generator Protection features: 25, 32, 40, 50/51, 27/59, 81 O/U
  • AGC-4 provides voltage and frequency adjust, base load / PF / load sharing / synchouronizer, auto start / stop control & generator CB control, SCADA Interface (Ethernet), fuel level indications & alarms, fuel tank fuel transfer control
  • Reverse compatibility for interface to legacy power modules
  • 100 kAIC, 4000A-Frame generator circuit breaker with LSIG trip unit
  • Multi-mode operation (Island (kW/kVAR sharing, Auto Mains Failure, Peak Shaving, Base Load Power, Export, zero power transfer, power management with multiple units)
  • Manual and automatic paralleling capability
  • Metering display: voltage, current, frequency, power factor, kW, WHM, kVAR, and synchouroscope

Quality

  • Factory testing of complete power module
  • CE Certified, NEMA, ISO and IEEE standards
  • O&M manuals

Similar New Power Solutions

XQ425
Mobile Generator Sets

XQ425

Rating Prime: 340 ekW (425 kVA)
Frequency: 50/60 Hz
Voltage: 120 - 600 V

XQC1200
Mobile Generator Sets

XQC1200

Rating: 1150kW (1438 kVA) Continuous
Frequency: 50/60 Hz
Voltage: 230 - 480 V

XQ570 Tier 4 Final - 455 ekW (568 kVA)
Mobile Generator Sets

XQ570 Tier 4 Final - 455 ekW (568 kVA)

Rating Prime: 455 ekW (568 kVA)
Frequency: 60 Hz
Voltage: 120 - 600 V

XQ35
Mobile Generator Sets

XQ35

Rating Prime: 27 ekW (35 kVA)
Frequency: 60 Hz
Voltage: 120 - 600 V

XQP150
Mobile Generator Sets

XQP150

Rating Prime: 150 kVA
Frequency: 50/60 Hz
Voltage: 127 - 480 V

XQP500
Mobile Generator Sets

XQP500

Rating Prime: 500 kVA
Frequency: 50/60 Hz
Voltage: 127 - 480 V

XQ60
Mobile Generator Sets

XQ60

Rating Prime: 47.5 ekW (60 kVA)
Frequency: 60 Hz
Voltage: 120 - 600 V

XQP300
Mobile Generator Sets

XQP300

Rating Prime: 300 kVA
Frequency: 50/60 Hz
Voltage: 127 - 480 V

XQP100
Mobile Generator Sets

XQP100

Rating Prime: 100 kVA
Frequency: 50/60 Hz
Voltage: 127 - 480 V

XQ125 Rental Power
Mobile Generator Sets

XQ125 Rental Power

Rating Prime: 100 ekW (125 kVA)
Frequency: 60 Hz
Voltage: 120 - 600 V