30 ekW Diesel Generator Set

Producing reliable power of 30 ekW at 60 Hz, our DE33 GC diesel generator set is designed to meet ISO 8528-5 transient response requirements.

Benefits

Installed Space

Requires less space for installation; leaves more room for your on-going operations

Hours

Ensures you can count on emergency power when it is needed

Prevents water accumulation

Enclosure designed to be waterproof for reliability and durability

Features at a Glance

Cat Generator Set Package
  • Cat generator set packages have been fully prototype tested
  • Accepts 100% block load in one step and meets NFPA 110 loading requirements
  • Conform to ISO 8528-5 steady state and transient response requirements
Cat Diesel Engine
  • Reliable, rugged, durable design
  • Field-proven in thousands of applications worldwide
  • Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum weight
A-Frame Alternator
  • Superior motor starting capability minimizes need for oversizing alternator
  • Designed to match performance and output characteristics of Cat diesel engines
  • Robust Class H insulation
GCCP 1.1 Control Panel
  • User-friendly interface and navigation
  • Scalable system to meet a wide range of installation requirement
  • Expansion modules and site-specific programming for specific customer requirements
Cooling System
  • Designed to operate in standard ambient temperatures up to 55°C (131°F)
  • Contact your Cat Dealer for specific ambient and altitude capabilities
Certifications
  • CE Certification Available
  • CIS Certification Available
One Safe Source
  • Components used in the generator set are selected based on seamless design integration to provide the optimum performance
  • The generator set is fully assembled at a Caterpillar facility following our quality guidelines
  • Each generator set package is tested before leaving the Caterpillar facility
  • Cat product support, including dealer service, parts and warranty covers the entire Cat power system
Worldwide Product Support
  • Cat dealers have over 1,800 dealer branch stores operating in 200 countries
  • Your local Cat dealer provides extensive post-sale support, including maintenance and repair agreements

Specifications

Full Specifications

Generator Set Specifications

Maximum Rating
30.0 ekW

Minimum Rating
30.0 ekW

Emissions/Fuel Strategy
Non Regulated

Voltage
220 to 480 Volts

Frequency
60 Hz

Speed
1800 rpm

Duty Cycle
Standby

Engine Specifications

Engine Model
Cat® C3.3, In-line 3, 4-cycle diesel

Bore
4.1 in

Stroke
5 in

Displacement
201.4 in³

Compression Ratio
19.25:1

Aspiration
Naturally Aspirated

Fuel System
Inline

Governor Type
Mechanical

Generator Set Dimensions

Length - Maximum
76.6 in

Width - Maximum
34.3 in

Height - Maximum
48.7 in

Dry Weight - Genset (maximum)
2114 lb

Equipment

Standard Equipment

Engine

  • C3.3, Inline 3 cylinder, 4 stroke diesel

Genset Control

  • GCCP 1.1

Governor

  • Mechanical governor

Alternator

  • A Frame standard alternator

Fuel Storage

  • Single wall 8 hour fuel tank

Enclosure

  • Cat GC enclosure

Air, Cooling & Exhaust

  • Enclosure silencer

General

  • Engine and alternator pre-paint, Caterpillar yellow
Optional Equipment

Certification

  • Certificate of Conformance
  • Australia, CIS, Gulf Certification

Alternator Requirements

  • Space heater

Auxiliary Supply Voltage

  • 120V

Fuel Storage

  • Dual wall 8 hour fuel tank
  • Low fuel level shutdown
  • Single wall tank with containment
  • Low fuel level alarm
  • High fuel level alarm

Genset Control

  • Battery charger
  • Volt free contacts for genset running
  • Volt free contacts for common alarm
  • Earth fault
  • Panel mounted audible alarm
  • USB to RS485 Communications device
  • Emergency stop with key
  • Earth leakage
  • Low coolant level shutdown
  • Coolant heater
  • Standby Pack (Smart Jacket water heater, Battery charger)
  • Battery

Circuit breaker

  • 3 Pole Circuit breaker 80A
  • 3 Pole Circuit breaker 63A
  • 3 Pole Circuit breaker 100A
  • 3 Pole Circuit breaker 125A
  • 3 Pole Circuit breaker 160A
  • 3 Pole Circuit breaker 200A
  • 4 Pole Circuit breaker 80A
  • 4 Pole Circuit breaker 63A
  • 4 Pole Circuit breaker 100A
  • 4 Pole Circuit breaker 125A
  • 4 Pole Circuit breaker 160A
  • 4 Pole Circuit breaker 200A
  • Circuit breaker padlock
  • Neutral earth link
  • Overload via alarm switch on breaker

Testing & Packaging

  • PGS Test report @ 1.0 power factor
  • PGS Test report @ 0.8 power factor

Similar New Power Solutions

C1.1 Generator Set
Diesel Generator Sets

C1.1 Generator Set

Maximum Rating: 9.5 kVA
Minimum Rating: 6.8 kVA
Emissions/Fuel Strategy: R96/EUIIIa Equivalent

C1.5 Generator Set
Diesel Generator Sets

C1.5 Generator Set

Maximum Rating: 13.5 kVA
Minimum Rating: 10.0 kVA
Emissions/Fuel Strategy: R96/EUIIIa Equivalent

C3.3 Generator Set
Diesel Generator Sets

C3.3 Generator Set

Maximum Rating: 65.0 kVA
Minimum Rating: 24.0 kVA
Emissions/Fuel Strategy: EU Stage II R96/EUIIIa

C2.2 Generator Set
Diesel Generator Sets

C2.2 Generator Set

Maximum Rating: 22.0 kVA
Minimum Rating: 13.0 kVA
Emissions/Fuel Strategy: R96/EUIIIa Equivalent

C4.4 Generator Set
Diesel Generator Sets

C4.4 Generator Set

Maximum Rating: 110 kVA
Minimum Rating: 50 kVA
Emissions/Fuel Strategy: EU Stage II & R96/EUIIIa

C7.1 ACERT
Diesel Generator Sets

C7.1 ACERT

Maximum Rating: 220 kVA
Minimum Rating: 135 kVA
Emissions/Fuel Strategy: Non Regulated, EU Stage IIIA

3512B Diesel Generator Set
Diesel Generator Sets

3512B Diesel Generator Set

Standby Rating: 1625/1600/1500 kVA
Prime Power Rating: 1500/1360 kVA
Emissions/Fuel Strategy: Low Fuel , Low Emissions

3512 Generator Set
Diesel Generator Sets

3512 Generator Set

Standby Rating: 1400/1250 kVA
Prime Power Rating: 1275/1150 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516B Generator Set
Diesel Generator Sets

3516B Generator Set

Standby Rating: 2250 kVA
Prime Power Rating: 2000 kVA
Emissions/Fuel Strategy: Low fuel, Low Emissions

3516 Diesel Generator Set
Diesel Generator Sets

3516 Diesel Generator Set

Standby Rating: 2000 kVA
Prime Power Rating: 1825 kVA
Emissions/Fuel Strategy: Low Fuel Consumption