MX350 Controller

ATS MX Contactor

Details

Voltage Unbalance on Dropout for Source 1 and Source 2
5 to 20% of nominal

Delay NeutralTransition Time Delays (DT,DW)
0-10 minutes

Control Power
120 VAC

Contact

Foley Equipment Sales

+1 (316) 943-4211

Request a Quote

Overview

The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.

Benefits

microprocessor

is standard with the entire CTE product family

Control Panel

interface provides local control and access to system information. Automation FlexLogic� with interlocking and programmable logic control

Features at a Glance

Features and Benefits
  • Dual Communications
    Built-in RS-485 serial and 10/100 base-T Ethernet
    Open protocols - Modbus RTU and Modbus TCP
  • Available to support Open, Closed and Delayed Transition
  • Small footprint
  • Graphical control panel
  • Multiple communication protocols
  • ¼ inch VGA color graphical display with embedded HELP menus
  • Status LED's indicating:
    ALARM - indicating a problem with the ATS or a user configured alarm condition is active
    TD DELAY - indicating the controller is timing before taking the next control action
    XFER INHIBIT - indicating the controller will not transfer to the other source without operator intervention
    SOURCE 1(S1) AVAILABLE LED - indicating power is present per user setpoints
    SOURCE 2 (S2) AVAILABLE LED - indicating power is present per user setpoints
    SOURCE 1 (S1) STATUS LED - indicating load is connected to S1 power
    SOURCE 2 (S2) STATUS LED - indicating load is connected to S2 power
  • User-Configurable setpoints for inputs and Outputs
  • Field modification of control features
  • Plant exerciser clock for 1 day, 1 week, 14 days, 28 days or 365 days. The time base of 365 days permits up to 24 events to be scheduled and the other time bases permit up to 24 events.
  • SYSTEM TESTS
    Fast Test - test with load, no time delays
    Transfer Load - test with load with time delays
    No Transfer - test without load, generator start only
  • Controller Power Supply utilizing the Universal Transformer Assembly (UTA) - provides 170Vdc to the controller and 24Vdc ungrounded to the power relays. The UTA also provides line voltages from 120Vac to 600Vac via an internal six position jumper array, 120Vac UPS input and 24Vdc input battery options.
  • Dual processor based with dedicated processor for high speed Serial or Ethernet connections
  • All signal in / out relays are isolated via DIN Mounted relay / terminal blocks
  • Elevator pre-signal contacts
  • Power quality metering
  • Elevator pre-signal

Specifications

Full Specifications

Controller Specifications

Voltage Unbalance on Dropout for Source 1 and Source 2
5 to 20% of nominal

Delay NeutralTransition Time Delays (DT,DW)
0-10 minutes

Control Power
120 VAC

Undervoltage Dropout for Source 1 and Source 2
75-99% of nominal

Undervoltage Restore for Source 1 and Source 2
85-100% of nominal

Overfrequency Dropout for Source 1 and Source 2
50.1 - 63 Hz

Source Sensing
120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A)

Delay for Engine Cool Down (U)
0-60 minutes

Underfrequency Restore for Source 1 and Source 2
45 - 59.5 Hz

Load Control Relay Contacts (2)
0-259 minutes

Overvoltage Dropout for Source 1 and Source 2
105 - 110% of nominal

Voltage Unbalance for Restore for Source 1 and Source 2
4 to 19% of nominal

Storage Temperature
(-40˚C - 90˚C )

Underfrequency Dropout for Source 1 and Source 2
45 - 59.9 Hz

Overfrequency Restore for Source 1 and Source 2
50 - 62.9 Hz

Delay Transfer to Nonpreferred Source (W)
0-5 minutes

Operating Temperature Ambient
(-20˚C to 50˚C)

Communications Interface - Optional
Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T)

Overvoltage Restore for Source 1 and Source 2
103 - 108% of nominal

Load Control Relay Contacts (1)
rated for 10A @ 24VDC or 120VAC

Technical Summary

Rating Range
Switch Dependent

Transfer Type
Application Dependent

Switch Type
Application Dependent

Equipment

Standard Equipment

Status LEDS for:

  • Transfer Inhibit
  • Active Alarms
  • Source 1 and 2 Availablity
  • Source 1 and 2 Connected
  • Time Delay Active

Graphical Display:

  • Color graphical display with USB Calibration/programming port and Embedded Help
  • Displays 256 time-tagged events with 1 ms resolution
  • Monitors over/under frequency, voltage conditions, frequency imbalance, and phase rotation
  • Provided detailed outage,test,and diagnostic reports

Ranges of Controls / Metering:

  • Programmable generator exerciser
  • Synchroscope
  • Contacts for Source 1 and Source 2 position indication as well as remote load test signals, and engine start delay
  • Source 1 and Source 2 In-phase monitor
  • Neutral, Engine Start, and Engine stop time delay timers

Testing and Certification

  • Conforms to EN 60947-1, EN 60947-6-1, EN 60255-26 (EN 50263), EN 5502 / CISPR22 / EN 61000-6-2 / EN 61000-6-4
  • Tested in accordance with:
    IEC 60068-2-30
    IEC 60068-2-1
    IEC 60068-2-2
    IEC 60255-22-1
    IEC 60255-22-2
    IEC 60255-22-3
    IEC 60255-22-4
    IEC 60255-22-5
    IEC 60255-22-6
    IEC 60255-25
    IEC 60529; IP54 (front),IP20(back)
    IEC 61000-4-11
  • Quality System:
    Manufactured under an ISO 9001 Registered Program
Optional Equipment

Option Package A:

  • Four (4) programmable inputs and four (4) outputs assignable to additional ATS features
  • Expanded diagnostics, high-speed 256 event capture, 365 days
  • Monitoring Software (local or remote), USB interface for uploading and downloading setup parameters
  • Full function ATS control with full sensing and control capabilities
  • Full complement of programmable ATS control switches AUTO / MAN, Preferred Source selector,Commit / No Commit Xfer, Transition Mode Select for Closed Transition switch models)

Option Package B:

  • Waveform capture, ten (10) channels, up to 256 cycles each sixteen (16) samples / sec.
  • Ten (10) customer programmable digital and ten (10)analog alarms.
  • Includes Option Package A features, plus
  • Auto Load Shed with voltage, frequency and kW triggers.
  • Twenty (20) channel data logger, customer configurable sample period from one (1) cycle to sixty (60) minutes.

Option Package C:

  • Includes Option B features, plus
  • Four (4) additional inputs and outputs (totaling eight (8) in & eight (8) out)

Option Package D:

  • Customized user control logic
  • Includes Option Package C features, plus
  • Four (4) additional inputs and outputs (totaling twelve (12) in & twelve (12) out)

Option Package M:

  • Configuration for Manual Operation only (Non-Automatic)

Similar New Power Solutions

MX150 Microprocessor Controller
ATS MX Contactor

MX150 Microprocessor Controller

Rating Range: Switch Dependent
Transfer Type: Application Dependent
Switch Type: Application Dependent

MX250 Microprocessor Controller
ATS MX Contactor

MX250 Microprocessor Controller

Rating Range: Switch Dependent
Transfer Type: Application Dependent
Switch Type: Application Dependent

CTS Series Automatic Transfer Switch
ATS MX Contactor

CTS Series Automatic Transfer Switch

Rating Range: 40 to 4000A
Transfer Type: Open transition
Switch Type: Contactor Based

CTG Series Automatic Transfer Switch
ATS MX Contactor

CTG Series Automatic Transfer Switch

Transfer Type: Open transition
Rating Range: 40-3000A
Switch Type: Contactor based

CTX Series Automatic Transfer Switch
ATS MX Contactor

CTX Series Automatic Transfer Switch

Rating Range: 40-400A
Transfer Type: Open transition
Switch Type: Contactor Based

CTE Series Automatic Transfer Switch
ATS MX Contactor

CTE Series Automatic Transfer Switch

Rating Range: 40-4000A
Transfer Type: Open / Closed / 4 position switch
Switch Type: Contactor Based

CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch
ATS MX Contactor

CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch

Switch Type: Contactor Based
Transfer Type: Open Transition with Service Entrance
Rating Range: 40-3000A

CTSM and CTGM Series Manual Transfer Switches
ATS MX Contactor

CTSM and CTGM Series Manual Transfer Switches

Rating Range: 40-4000A
Transfer Type: Open / Manual
Switch Type: Contactor Based