MX250 Microprocessor Controller

ATS MX Contactor

Details

Rating Range
Switch Dependent

Transfer Type
Application Dependent

Switch Type
Application Dependent

Contact

Foley Equipment Sales

+1 (316) 943-4211

Request a Quote

Overview

The MX250 microprocessor is standard with the entire CTS product family. The MX250 Series includes all the standard features of the MX150 Controller while offering expanded programmability and field adaptability. The high reliability and ease of unattended operation makes it ideal to use in a wide range of mission critical applications.

Benefits

microprocessor

is standard with the entire CTS product family

Reliability

and ease of unattended operation makes it ideal to use in a wide range of mission critical applications

Features at a Glance

Features and Benefits
  • Available to support ALL transfer modes:
    –Open, Delayed and Closed Transition
  • User-friendly programmable engine exerciser,with or without load, at ANY interval in a one-year period
  • A wide variety of operating voltages available in a single controller for most domestic and international applications
  • Real-time display of ATS status, including active timer(s)
  • Multiple levels of user-defined password protection
  • Serial communications allowing connectivity with other ATS's, Caterpillar® Switchgear, and SCADA systems
  • Time-tested synchronous logic automatically measures phase angle and frequency allowing disturbance-free transfer
  • Unsurpassed statistical ATS/System monitoring available in real-time
  • Elevator pre-signal contacts automatically bypassed if the selected source fails, minimizing time an elevator is without power
  • Universal Motor Disconnect (UMD) sends a pre-signal, post-signal or both to any motor control center. Not bypassed in an outage,the UMD ensures safety in the event of a single phase loss
  • Voltage unbalance detection standard
  • Also includes all standard MX150 features
  • Back-lit/temperature compensated LCD display (includes the display of source voltage and frequency, exercise time, delay options and source condition)
  • Close differential 3-phase under-voltage sensing of source 1, factory standard setting 90% pickup, 80% dropout; under-frequency sensing of source 1 factory setting 95% pickup;voltage and frequency sensing of source 2,factory standard setting 90% pickup voltage,95% pickup frequency.
    All factory settings are operator adjustable.
  • LED indicators for ATS position and source availability
  • Plant exerciser clock (configured for 1, 7, 14 or 28 day run selections)
  • Built-in time delays with count-down display
  • Push button to bypass time delay transfer/retransfer
  • Transfer/commit/no commit selection In-phase monitor
  • Event logging (last 16 events)
  • A test is standard (fast test/load/no load) to simulate source 1 failure – automatically bypassed should source 2 fail.

Specifications

Full Specifications

Technical Summary

Rating Range
Switch Dependent

Transfer Type
Application Dependent

Switch Type
Application Dependent

Controller Specifications

Undervoltage Dropout for Source 1 and Source 2
75-98% of nominal

Undervoltage Restore for Source 1 and Source 2
85-100% of nominal

Underfrequency Dropout for Source 1 and Source 2
90-100% of nominal

Delay for Engine Cool Down (U)
0-60 minutes

Delay Transfer to Nonpreferred Source (W)
0-5 minutes

Delay NeutralTransition Time Delays (DT,DW)
0-10 minutes

Storage Temperature
(-30˚C - 75˚C ), -22˚F - 167˚F

Operating Temperature Ambient
40 - 400 amp molded shell (-20˚C to 65˚C) , -4˚F to 149˚F <br>40 - 4000 amp all others (-20˚C to 60˚C), -4˚F to 149˚F

Equipment

Standard Equipment

Performance

  • ESD immunity test per EN61000-4-2 Class B(Level 4)
  • Electrical fast transient/burst immunity test perEN61000-4-4
  • Conducted and Radiated Emissions per EN55022Class B (CISPR11) (Exceeds EN55011 & MILSTD461 Class 3)
  • Voltage dips and interruption immunity EN61000-4-11
  • Conducted immunity test per EN61000-4-6(ENV50141)
  • Ringing wave immunity per IEEE 472(ANSIC37.90A)
  • Surge immunity test per EN61000-4-5 IEEE C62.41
  • UL, CSA and IEC listed
  • Radiated RF, electromagnetic field immunitytest per EN61000-4-3 (ENV50140) 10v/m

User Friendly Operation

  • Weather and tamper resistant touchpad
  • Through-the-door programming and display
  • Multipurpose display: LEDs for continuous monitoring of switch position and source availability; a four line by twenty character LCD display for settings, functions, programming and annunciation
  • Simplified keypad entry – menu-driven system is designed for ease of use
  • Built-in diagnosis with displays for ease of troubleshooting

Additional Features

  • User settings are unaffected by power outages
  • Built-in programmable exerciser uses separate microcontroller with independent battery back-up to serve as clock/calendar – battery failure will not affect switch operation
  • Built-in electrical operator protection
  • Inputs are optoisolated for high electrical immunity to transients and noise
  • Source connection and transfer data logging
  • Separate line voltage components for controller isolation
  • Watchdog circuit for microprocessor operation

Similar New Power Solutions

MX150 Microprocessor Controller
ATS MX Contactor

MX150 Microprocessor Controller

Rating Range: Switch Dependent
Transfer Type: Application Dependent
Switch Type: Application Dependent

MX350 Controller
ATS MX Contactor

MX350 Controller

Voltage Unbalance on Dropout for Source 1 and Source 2: 5 to 20% of nominal
Delay NeutralTransition Time Delays (DT,DW): 0-10 minutes
Control Power: 120 VAC

CTS Series Automatic Transfer Switch
ATS MX Contactor

CTS Series Automatic Transfer Switch

Rating Range: 40 to 4000A
Transfer Type: Open transition
Switch Type: Contactor Based

CTG Series Automatic Transfer Switch
ATS MX Contactor

CTG Series Automatic Transfer Switch

Transfer Type: Open transition
Rating Range: 40-3000A
Switch Type: Contactor based

CTX Series Automatic Transfer Switch
ATS MX Contactor

CTX Series Automatic Transfer Switch

Rating Range: 40-400A
Transfer Type: Open transition
Switch Type: Contactor Based

CTE Series Automatic Transfer Switch
ATS MX Contactor

CTE Series Automatic Transfer Switch

Rating Range: 40-4000A
Transfer Type: Open / Closed / 4 position switch
Switch Type: Contactor Based

CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch
ATS MX Contactor

CTGSE & CTGDSE Series Service Rated Entrance Rated Automatic Transfer Switch

Switch Type: Contactor Based
Transfer Type: Open Transition with Service Entrance
Rating Range: 40-3000A

CTSM and CTGM Series Manual Transfer Switches
ATS MX Contactor

CTSM and CTGM Series Manual Transfer Switches

Rating Range: 40-4000A
Transfer Type: Open / Manual
Switch Type: Contactor Based