ATC-300+ CONTROLLER
ATS ATC Breaker / Contactor
Details
Rating Range
120 to 600V, single phase and three phase @ 50/60 Hz
Transfer Type
Switch application dependent
Switch Type
Switch application dependent
Overview
The ATC-300+ is a comprehensive and multifunctional microprocessor-based ATS controller. It is a compact and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels. The ATC-300+ Controller provides programmed flexibility to address the needs of any system. It operates from all system voltages between 120 to 600V, single-phase and three-phase at 50 or 60 Hz. In addition, a period of no control power is provided. The controller monitors the condition of the three-phase line-to-line voltage and frequency of Source 1 and Source 2 power sources and can be programmed for single-phase operation. The ATC-300+ Controller provides the intelligence to ensure that the ATS operates properly through a series of programmed sensing and timing functions.
Benefits
is a comprehensive and multifunctional microprocessor-based ATS controller
and self-contained panel-mounted device that is designed to replace traditional relay and solid-state logic panels.
Features at a Glance
- Product Features
-
- Auxiliary relay contacts:
- Source 1 present 2NO and 2NC
- Source 2 present 2NO and 2NC
- Source 1 and source 2 sensing:
- Undervoltage / underfrequency
- Overvoltage / overfrequency
- Three-phase rotation protection
- Three-phase voltage unbalance/loss
- Pre-transfer signal contacts 1NO and 1NC
- Go to emergency (Source 2)
- Seven field-programmable time delays
- LCD-based display for programming, system diagnostic and help message display
- Mimic diagram with source available and connected LED indication
- Time-stamped history log
- System test pushbutton
- Programmable plant exercise (off, daily, 7,14 and 28 day) interval selectable run time 0-600 minutes no load/load with fail-safe
- Integral overcurrent protection (optional)
- In-phase transition
- Stainless steel cover for controller (optional)
- Communications via RS-232 or Modbus through an integrated RS-485 port (optional)
Specifications
Full Specifications
- Technical Summary
-
Rating Range
120 to 600V, single phase and three phase @ 50/60 HzTransfer Type
Switch application dependentSwitch Type
Switch application dependent
- ATC Controller Specifications
-
Input Control Voltage
65 to 145 Vac 50/60 hZVoltage Measurements of Utility
Source 1 VAB Source 2 VAB<br>Source 1 VAC Source 2 VBC<br>Source 1 VCA Source 2 VCAVoltage Measurement Range
0 to 790 VAC rms (50/60 Hz)Voltage Measurement Accuracy
+/-2% of nominal input voltageFrequency Measurements Of
Source 1 and Source 2Frequency Measurement Range
40 Hz to 70 HzFrequency Measurement Accuracy
+/- 0.1 HzUndervoltage Dropout
50% to 90% of nominal voltageUndervoltage Pickup
(Dropout +2%) to 99% of the nominal system voltageUnderfrequency Dropout Range
90 to 97% of the nominal system frequencyUnderfrequency Pickup Range
(Dropout +1 Hz) to 99% of the nominal system frequencyOverfrequency Dropout Range
103 to 110% of the nominal system frequencyOverfrequency Pickup Range
101% to (dropout - 1 Hz) of the nominal system frequencyOperating Temperature Range
-20 to 70 degree C (-4 to +158 degree F)Storage Temperature Range
-30 to 85 degree C (-22 to +185 degree F)Operating Humidity
0 to 95% relative humidity (noncondensing)Operating Environment
Resistant to ammonia, methane, nitrogen,hydrogen and hydrocarbonsGenerator Start Relay
5A, 1/6 hp @ 250 Vac Vac 5A @ 30 Vdc with a 150W maximum loadK1, K2 Relays
<br>10A, 1-3 hp @ 250 Vac</br><br>10A@30 Vdc</br>Applicable Testing
UL-recognized component<br>Meets intent of UL 991 & UL 1008<br>Meets IEC 1000-4-2, 1000-4-3, 1000-4-4Applicable Testing Continued
1000-4-5, 1000-4-6, 1000-4-11<br>CISPR 11, Class A<br>FCC Part 15, Class A<br>CSS 22.2-178Enclosure Compatibility
NEMA 1, NEMA 3R and NEMA 12<br>UV-resistant ATC-300+ faceplate